R-407C vs R-22 Refrigerant | KOOLIN

REFRIGERANT RETROFIT GUIDE

R-407C vs R-22 Refrigerant

A comprehensive technical retrofit guide for converting legacy R-22 air conditioning and commercial heat pump systems to non-ozone-depleting R-407C. Master lubricant flush, expansion valve adjustments, and operating pressures.

KOOLIN R-407C Refrigerant 25 lb cylinder and carton
ZERO-ODP HFC RETROFIT

R-407C · 25 lb Cylinder

A1 non-flammable ternary blend (R-32 / R-125 / R-134a) exhibiting operating pressures and cooling capacities closely matching R-22. Requires POE lubricant conversion.

View KOOLIN R-407C Cylinders →
LEGACY HCFC (PHASED OUT)

R-22 (Freon 22)

Class II ozone-depleting HCFC refrigerant prohibited from virgin manufacture and import under the Clean Air Act. Servicing relies on existing recovered/reclaimed stocks.

Phase-out complete (Replaced by R-407C)

Side-by-Side Technical Comparison

Technical Parameter R-407C (Suva 407C) R-22 (Freon 22)
ASHRAE Safety Group A1 (Non-Flammable) A1 (Non-Flammable)
Chemical Classification HFC Blend (23% R-32 / 25% R-125 / 52% R-134a) Pure HCFC (Chlorodifluoromethane)
Ozone Depletion Potential (ODP) 0.00 (Zero Ozone Depletion) 0.055 (Ozone Depleting)
Global Warming Potential (GWP) 1,774 1,810
Standard Net Cylinder Weight 25 lb (Factory-Sealed Cylinder) Legacy 30 lb Cylinder
Operating Pressures Close match (~95% to 105% of R-22) Baseline standard (~225-260 PSI discharge)
Temperature Glide ~9°F to 11°F (Moderate glide, liquid charging mandatory) 0°F (Single component, vapor or liquid charging)
Required Lubricant POE (Polyolester) Oil (Residual MO must be < 5%) Mineral Oil (MO) or Alkylbenzene (AB)
Cooling Capacity & Efficiency Matches R-22 within ±5% across AC applications Baseline standard

Is R-407C a direct drop-in replacement for R-22?

No. R-407C cannot be directly topped off into an R-22 system without complete lubricant conversion. Because R-407C is insoluble in traditional mineral oil, failure to flush and replace the oil with POE will prevent oil return, resulting in compressor seizure.

A proper retrofit procedure requires: 1) Full recovery of all existing R-22, 2) Flushing lubricant until residual mineral oil is under 5%, 3) Replacing liquid line filter-driers and elastomeric seals, 4) Charging R-407C strictly in the liquid phase to preserve blend composition, and 5) Relabeling the equipment with R-407C and POE identifiers per EPA guidelines.